A 95mm² copper cable with XLPE insulation (90°C rating) in air has a base current of 350A at 30°C. If the ambient air temperature in a boiler room is 55°C, the correction factor from IEC 60364-5-52 might be 0.75. The derated capacity = $350 \times 0.75 = 262.5A$. Ignoring this could cause premature insulation failure within months.
This is where come to the rescue.
Leave space. Use ventilated trays. Derate less if cables are flat-spaced rather than trefoil (triangular) packed. 3. Soil Thermal Resistivity (Buried Cables) Burying cables solves aesthetic and mechanical problems but introduces a complex thermal variable: the soil's ability to conduct heat away from the cable. cable derating factors